Seperti di email Bapak sebelumnya bahwa terdapat alignment dan FSC error. Merujuk pada user manualnya, hal ini kemungkinan karena terjadi perbedaan settingan komunikasi antara ethernet/IP module dengan switch port nya. Berikut langkah-langkah troubleshootingnya (ENET-UM001I-EN-P hal 156):
" If These errors are counted:
·Alignment
·FCS
·Carrier Sense
Then, a duplex mismatch exists between your EtherNet/IP module and the switch port.
To clear the duplex mismatch:
a.Configure the EtherNet/IP module and the corresponding Ethernet switch port for a forced operation, not autonegotiation. See Configure the Module with RSLinx Software on page 48.
b.Verify that the firmware revision of your Logix controller and switch or converter are identical.
c.If the revisions are not identical, replace the controller, switch or converter so that they match."
Salam,
Boris
________________________________
From: taufik hidayah <topik_jbi@yahoo.com>
To: "Migas_Indonesia@yahoogroups.com" <Migas_Indonesia@yahoogroups.com>
Sent: Wednesday, August 10, 2011 1:12 PM
Subject: Re: [Oil&Gas] [INST] 1756-ENBT/A Lost connection ke HMI Wonderware
�
Terimakasih atas tanggapan bapak Boris,
Tapi maaf pak,saya tidak menemukan screenshot yg bapak maksud..
klo dari referensi saya udah dapat dari situs rockwell sendiri mengenai troubleshooting ethernet module.
trims,
Taufik
Portal Industri : http://www.migas-indonesia.com
No E-mail (Web) : Migas_Indonesia-nomail@yahoogroups.com
Daily Digest : Migas_Indonesia-digest@yahoogroups.com
Individual Mail : Migas_Indonesia-normal@yahoogroups.com
Administrator : Migas_Indonesia-owner@yahoogroups.com
Mirror : http://groups.google.com/group/Migas-Indonesia-Google
Untuk pergantian alamat email dan pengiriman attachment
silahkan hubungi webmaster(at)migas-indonesia.com
HAPUS BAGIAN EMAIL YANG TIDAK DIPERLUKAN SEWAKTU REPLY
PENGIRIMAN ATTACHMENT KE MILIS HARUS MELEWATI ADMINISTRATOR
--------------------------------------------------------------




No comments:
Post a Comment