Sependek yg saya tahu, mengutip dari NFPA 14
7.8.1 Minimum Design Pressure for Hydraulically Designed Systems.
7.8.1.1 Hydraulically designed standpipe systems shall be designed to provide the waterflow rate required by Section 7.10
at a minimum residual pressure of 100 psi (6.9 bar) at the outlet of the hydraulically most remote 65-mm (21⁄2-in.) hose
connection and 4.5 bar (65 psi) at the outlet of the hydraulically most remote 38-mm (11⁄2-in.) hose station.
Kalau dalam spec kami:
… the pressure shall never exceed 12 barg for 1" and 7 barg for 1-½" systems. If necessary, a pressure control valve can be installed.
Mungkin rekan dari lapangan bisa sharing apakah pressure setinggi ini akan menyebabkan hose menjadi liar waktu digunakan. CMIIW
From: hadi muttaqien <hadimtq2000@yahoo.com>
To: "Migas_Indonesia@yahoogroups.com" <Migas_Indonesia@yahoogroups.com>
Sent: Wednesday, August 17, 2011 7:54 PM
Subject: Re: [Oil&Gas] Fire Fighting (Sprinkler & Pillar Hydrant)
Pak Imam,
Untuk Sprinkler ada dipasang PRV/MCV tapi untuk Pillar Hydrant tidak, saya masih mencari referensi, koq tekanan kerja 8,5-10 bar ? apa gak pontang-panting mengoperasikannya? Terimakasih juga untuk tanggapan dari rekan2 lainnya.
Wassalam,
Hadi M.
Untuk Sprinkler ada dipasang PRV/MCV tapi untuk Pillar Hydrant tidak, saya masih mencari referensi, koq tekanan kerja 8,5-10 bar ? apa gak pontang-panting mengoperasikannya? Terimakasih juga untuk tanggapan dari rekan2 lainnya.
Wassalam,
Hadi M.
__._,_.___
--------------------------------------------------------------
Portal Industri : http://www.migas-indonesia.com
No E-mail (Web) : Migas_Indonesia-nomail@yahoogroups.com
Daily Digest : Migas_Indonesia-digest@yahoogroups.com
Individual Mail : Migas_Indonesia-normal@yahoogroups.com
Administrator : Migas_Indonesia-owner@yahoogroups.com
Mirror : http://groups.google.com/group/Migas-Indonesia-Google
Untuk pergantian alamat email dan pengiriman attachment
silahkan hubungi webmaster(at)migas-indonesia.com
HAPUS BAGIAN EMAIL YANG TIDAK DIPERLUKAN SEWAKTU REPLY
PENGIRIMAN ATTACHMENT KE MILIS HARUS MELEWATI ADMINISTRATOR
--------------------------------------------------------------
Portal Industri : http://www.migas-indonesia.com
No E-mail (Web) : Migas_Indonesia-nomail@yahoogroups.com
Daily Digest : Migas_Indonesia-digest@yahoogroups.com
Individual Mail : Migas_Indonesia-normal@yahoogroups.com
Administrator : Migas_Indonesia-owner@yahoogroups.com
Mirror : http://groups.google.com/group/Migas-Indonesia-Google
Untuk pergantian alamat email dan pengiriman attachment
silahkan hubungi webmaster(at)migas-indonesia.com
HAPUS BAGIAN EMAIL YANG TIDAK DIPERLUKAN SEWAKTU REPLY
PENGIRIMAN ATTACHMENT KE MILIS HARUS MELEWATI ADMINISTRATOR
--------------------------------------------------------------
.
__,_._,___




No comments:
Post a Comment